GE 745 Instruction Manual page 114

Transformer protection system
Hide thumbs Also See for 745:
Table of Contents

Advertisement

AUTO-CONFIGURATION
Transformer
Wdg.
Connection
type
Y/d330°/
1
d210°
2
3
D/d0°/d0°
1
2
3
D/d0°/d120°
1
2
3
D/d0°/d240°
1
2
3
D/d0°/y30°
1
2
3
5–18
Table 5–1: Transformer types (Sheet 6 of 11)
Voltage
Phase
phasors
shift
WYE
330° lag
DELTA
330° lag
DELTA
120° lag
210° lag
DELTA
DELTA
DELTA
DELTA
120° lag
DELTA
120° lag
DELTA
120° lag
DELTA
240° lag
DELTA
240° lag
DELTA
240° lag
DELTA
DELTA
WYE
330° lag
30° lag
Transformer
Wdg.
type
Y/d330°/
d330°
D/d0°/d60°
D/d0°/d180°
D/d0°/d300°
D/d0°/y150°
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
Connection
Voltage
phasors
1
WYE
2
DELTA
330° lag
3
DELTA
330° lag
1
DELTA
2
DELTA
3
DELTA
60° lag
1
DELTA
2
DELTA
3
DELTA
180° lag
1
DELTA
2
DELTA
3
DELTA
300° lag
1
DELTA
2
DELTA
3
WYE
150° lag
Phase
shift
330° lag
60° lag
60° lag
180° lag
180° lag
300° lag
300° lag
210° lag

Hide quick links:

Advertisement

Table of Contents
loading