TYPICAL WIRING
3–8
Table 3–1: Rear terminal assignments (Sheet 1 of 2)
Term.
Description
Analog interface
A1
Analog input +
A2
Analog input –
A3
Tap position (+)
A4
Tap position (–)
A5
Analog output (common)
A6
Analog output 1 (+)
A7
Analog output 2 (+)
A8
Analog output 3 (+)
A9
Analog output 4 (+)
A10
Analog output 5 (+)
A11
Analog output 6 (+)
A12
Analog output 7 (+)
Communications and RTD inputs
B1
Computer RS485 (+) / RS422 (Rx+)
B2
Computer RS485 (–) / RS422 (Rx–)
B3
Computer RS485/RS422 (common)
B4
RS422 (Tx+)
B5
RS422 (Tx–)
B6
External RS485 (+)
B7
External RS485 (–)
B8
IRIG-B +
B9
IRIG-B –
B10
RTD 1 hot
B11
RTD 1 compensation
B12
RTD 1 return
Logic inputs 9 to 16 and VT input
C1
Logic input 9 (+)
C2
Logic input 10 (+)
C3
Logic input 11 (+)
C4
Logic input 12 (+)
C5
Logic input 13 (+)
C6
Logic input 14 (+)
C7
Logic input 15 (+)
C8
Logic input 16 (+)
C9
Reserved
C10
Reserved
C11
VT input
C12
VT input
Logic inputs 1 to 8 and dedicated inputs
D1
Logic input 1 (+)
D2
Logic input 2 (+)
D3
Logic input 3 (+)
D4
Logic input 4 (+)
Term.
Outputs and ground CT N2
E1
Output 1: solid state trip (+)
E2
Output 2: trip relay (NO)
E3
Output 3: trip relay (NO)
E4
Output 4: trip relay (NO)
E5
Output 5: trip relay (NO)
E6
Output 6: auxiliary relay (NO)
E7
Output 6: auxiliary relay (NC)
E8
Output 7: auxiliary relay (NO)
E9
Output 8: auxiliary relay (NO)
E10
Output 8: auxiliary relay (NC)
E11
Output 9: service relay (common)
E12
Ground: winding 2/3 CT
Outputs and ground CT N2
F1
Output 1: solid state trip (–)
F2
Output 2: trip relay (common)
F3
Output 3: trip relay (common)
F4
Output 4: trip relay (common)
F5
Output 5: trip relay (common)
F6
Output 6: auxiliary relay (common)
F7
Output 7: auxiliary relay (NO)
F8
Output 7: auxiliary relay (NC)
F9
Output 8: auxiliary relay (common)
F10
Output 9: service relay (NO)
F11
Output 9: service relay (NC)
F12
Ground: winding 2/3 CT
CT inputs and 745 grounding
G1
Phase A: winding 1 CT
G2
Phase B: winding 1 CT
G3
Phase C: winding 1 CT
G4
Phase A: winding 2 CT
G5
Phase B: winding 2 CT
G6
Phase C: winding 2 CT
G7
Phase A: winding 3 CT
G8
Phase B: winding 3 CT
G9
Phase C: winding 3 CT
G10
Ground: winding 1/2 CT
G11
745 filter ground
G12
745 safety ground
CT and VT inputs / power
H1
Phase A: winding 1 CT
H2
Phase B: winding 1 CT
H3
Phase C: winding 1 CT
H4
Phase A: winding 2 CT
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
Description

Hide quick links:

Advertisement

Table of Contents
loading