D Isplay - GE 745 Instruction Manual

Transformer protection system
Hide thumbs Also See for 745:
Table of Contents

Advertisement

HARDWARE INTERFACE
4.1.2
Display
4.1.3
LEDs
4.1.4
LED Indicators
4.1.4.1 745 Status
4–2
All messages are displayed in English on the 40-character liquid crystal display, which is
backlit for visibility under varied lighting conditions. When the keypad and display are not
actively being used, the screen sequentially displays up to 30 user-selected default
messages providing system information. These messages appear after a time of inactivity
that is programmable by the user. Pressing any key after default messages have appeared
will return the display to the last message displayed before the default messages
appeared. Trip and alarm condition messages automatically override default messages. All
display pixels are illuminated briefly during power up self-testing, and can be energized by
pressing any key when no trips or alarms are active.
Front panel indicators are grouped in three columns: Relay Status, which provides
information about the state of the 745; System Status, which provides information about
the state of the transformer and the power system; and Output Status, which provides
details about abnormal conditions that have been detected. The color of each indicator
conveys information about its importance:
GREEN (G): indicates a general condition
AMBER (A): indicates an alert condition
RED (R): indicates a serious alarm or warning
RELAY IN SERVICE: The In Service LED is on when relay protection is operational. The
indicator is on only if all of the following conditions are met:
The
S1 745 SETUP
"Programmed".
The
S6 TESTING
set to "Disabled".
The
S6 TESTING

setpoint is set to "Disabled".
No self-test errors which have an effect on protection have been detected.
Code programming mode is inactive.
Factory service mode is disabled.
SELF-TEST ERROR: The Self-Test Error LED is on when any of the self-diagnostic tests,
performed either at power-on or in the background during normal operation, has
detected a problem with the relay.
TEST MODE: The Test Mode LED indicator is on when any of the 745 testing features
has been enabled. The indicator is on if any of the following conditions are met:
The
S6 TESTING
set to "Enabled".
The
S6 TESTING

setpoint is "Enabled".
INSTALLATION
745 SETPOINTS


OUTPUT RELAYS
FORCE OUTPUT RELAYS FUNCTION
SIMULATION
SIMULATION SETUP
OUTPUT RELAYS
FORCE OUTPUT RELAYS FUNCTION
ANALOG OUTPUTS
FORCE ANALOG OUTPUTS FUNCTION
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
setpoint is set to
setpoint is
SIMULATION FUNCTION
setpoint is