TARGET AND FLASH MESSAGES
Event message
EEPROM Memory
Clock Not Set
Emulation Software
Int Temperature
Flexlogic Equation
DSP Processor
Bad Xfmr Settings
IRIG-B Signal
Setpt Access Denied
Ambient Temperature
Self-Test Warning 7
6–26
Table 6–4: Self-test error interpretation (Continued)
Target message
Self-Test Warning 2
Replace Immediately
Clock Not Set
Program Date/Time
Self-Test Warning 4
Replace Immediately
Unit Temp. Exceeded
ServiceCheckAmbient
Flexlogic Eqn Error
Consult User Manual
Self-Test Warning 6
Replace Immediately
Bad Xfmr Settings
Consult User Manual
IRIG-B Error
Consult User Manual
Setpoint Access Denied
Consult User Manual
Amb. Temp. Exceeded
Check Ambient
Self-Test Warning 7
Call Service
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
Severity
Major
This error is caused by detection of
corrupted location in the 745 data
memory which cannot be self-
corrected. Errors that can be
automatically corrected are not
indicated. Any function of the 745 is
susceptible to maloperate from this
failure.
Minor
This error is caused when the 745
detects that the real-time clock is
not running. Under this condition,
the 745 will not be able to maintain
the current time and date. This
would normally occur if backup
power for the clock is lost and
control power is removed from the
745. Even if control power is
restored, the clock will not operate
until the time and/or date are
programmed via the
CLOCK
menu.

Minor
This error is caused by development
software being loaded in the relay.
Minor
The relay has detected an
unacceptably low
(< –40ªC) or high (> 85°C)
temperature inside the unit.
Major
This error is caused when an error in
FlexLogic™ is detected. No feature of
the 745 that is controlled by
FlexLogic will operate when this
failure occurs.
Programming correct FlexLogic
equations will remove this error.
Major
This error is caused when
communications with the internal
digital signal processor is lost. Most
of the monitoring capability of the
745 (including all measurement of
current) will be lost when this failure
occurs.
Major
This error is caused when the 745
determines that the transformer
configuration programmed via
setpoints does not correspond to a
realistic physical system.
Minor
This error is caused when the IRIG-B
signal type selected does not match
the format code being injected into
the IRIG-B terminals.
Minor
This error is caused when the
passcode is entered incorrectly three
times in a row from either the front
panel or any of the communication
ports. This error may be removed by
entering the correct passcode.
Minor
This error is caused when ambient
temperature is out of range.(–50 to
250°C inclusive).
Minor
This warning is caused by 745
microprocessor reset forced by
watchdog circuit.
Cause
S1 745 SETUP