CHAPTER 5: SETPOINTS
Transformer
Wdg.
Connection
type
D/d240°/
1
d240°
2
3
D/d240°/
1
y210°
2
3
D/d300°/
1
d180°
2
3
D/y30°/d240°
1
2
3
D/y30°/y210°
1
2
3
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Table 5–1: Transformer types (Sheet 9 of 11)
Voltage
Phase
phasors
shift
DELTA
240° lag
DELTA
240° lag
DELTA
240° lag
DELTA
DELTA
120° lag
240° lag
WYE
150° lag
210° lag
DELTA
300° lag
DELTA
300° lag
DELTA
120° lag
180° lag
DELTA
WYE
330° lag
30° lag
DELTA
120° lag
240° lag
DELTA
WYE
330° lag
30° lag
WYE
150° lag
210° lag
Transformer
Wdg.
type
D/d240°/y30°
1
0°
2
0°
3
0°
D/d300°/d0°
1
2
3
D/y30°/d60°
1
0°
2
3
0°
D/y30°/y30°
1
2
3
0°
D/y150°/d0°
1
2
3
AUTO-CONFIGURATION
Connection
Voltage
phasors
DELTA
DELTA
120° lag
240° lag
WYE
330° lag
30° lag
DELTA
300° lag
DELTA
300° lag
DELTA
300° lag
0°
DELTA
WYE
330° lag
30° lag
DELTA
300° lag
60° lag
DELTA
WYE
330° lag
30° lag
WYE
330° lag
30° lag
DELTA
WYE
210° lag
150° lag
DELTA
0°
Phase
shift
0°
0°
0°
0°
0°
0°
5–21
Need help?