GE 745 Instruction Manual page 175

Transformer protection system
Hide thumbs Also See for 745:
Table of Contents

Advertisement

CHAPTER 5: SETPOINTS
Note
NOTE
5.6.10.2 Underfrequency
UNDERFREQUENCY []
1
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
We strongly recommend the use of either the voltage, current, or both, signals for
supervision. If no supervising conditions are enabled, the element could produce
undesirable operation!
PATH: SETPOINTS
S4 ELEMENTS

UNDERFREQUENCY 1
FUNCTION: Disabled
UNDERFREQUENCY 1
MESSAGE
RLYS (1-8): --------
UNDERFREQUENCY 1
MESSAGE
TARGET: Self-Reset
CURRENT SENSING:
MESSAGE
Enabled
MINIMUM OPERATING
MESSAGE
CURRENT: 0.20 x CT
MINIMUM OPERATING
MESSAGE
VOLTAGE: 0.50 x VT
UNDERFREQUENCY 1
MESSAGE
PICKUP: 59.00 Hz
UNDERFREQUENCY 1
MESSAGE
DELAY: 1.00 s
UNDERFREQUENCY 1
MESSAGE
BLOCK: Disabled
MINIMUM OPERATING CURRENT: Enter the minimum value of winding 1 phase A
current (in units of relay nominal current) required to allow the underfrequency
element to operate.
MINIMUM OPERATING VOLTAGE: Enter the minimum value of voltage (in units of relay
nominal voltage) required to allow the underfrequency element to operate.
UNDERFREQUENCY 1(2) PICKUP: Enter the frequency (in Hz) below which the
underfrequency 1 element will pickup and start the delay timer.
UNDERFREQUENCY 1(2) DELAY: Enter the time the frequency remains below the
pickup level before element operation.
FREQUENCY
UNDERFREQUENCY 1(2)

Range:
Range:
Range:
Range:
Range:
Range:
Range:
Range:
Range:
S4 ELEMENTS
Enabled, Disabled
1 to 8
Self-Reset, Latched, None
Enabled, Disabled
0.05 to 1.00 x CT in steps of
0.01
0.10 to 0.99 x CT in steps of
0.01
45.00 to 59.99 Hz in steps of
0.01
0.00 to 600.00 s in steps of 0.01
Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled
5–79