PROTECTION SCHEMES
7.5
Protection Schemes
7.5.1
Precaution
CAUTION
7.5.2
Harmonic Restrained Percent Differential
7.5.2.1 Description
7.5.2.2 Minimum Pickup
Note
NOTE
7–16
Keep track of modifications/changes made to settings during the course of these
commissioning steps and ensure that all settings are returned to the 'in-service' values
at the end of the tests.
The harmonic restrained percent differential element setpoints are located in
DIFFERENTIAL
PERCENT DIFFERENTIAL

ensure that trip relay(s) and auxiliary relays are operated by element under test only. With
a multimeter, monitor the appropriate output contact(s) per intended settings of the
FlexLogic™. Refer to the relay settings to find out which relay(s) should operate when a
given element operates.
The minimum pickup of the phase A element is measured by applying a fundamental
frequency AC current to terminals H1 and G1, winding 1 phase A. Monitor the appropriate
trip and auxiliary contact(s) as the current is increased from 0 A. Compare the current value
at which operation is detected against the
DIFFERENTIAL
PERCENT DIFFERENTIAL PICKUP

normally set quite low, fine control of the current signal will be required to obtain accurate
results.
The currents in the winding may be phase shifted or may have the zero-sequence
component removed due to auto-configuration (see Auto-configuration on page 5–6). As
an alternate to calculating to relation of input current to differential current, the differential
current is displayed in
A2 METERING
displayed value is the same as the minimum pickup setting when the element operates.
 Check that the Trip and Message LEDs are flashing and one of the
following trip messages is displayed:
LATCHED a: Percent Differential, or OPERATED a: Percent
Differential
The above messages will indicate either
ELEMENTS
DIFFERENTIAL

TARGET
setting.
To independently verify that auto-configuration causes the currents to be as measured,
follow the rules outlined in the steps below.
 Look up transformer type in Table 5–1: Transformer types on page 5–
13.
CHAPTER 7: COMMISSIONING
. Disable all other protection elements to
S4 ELEMENTS

setpoint. Since the operating point is
CURRENT
DIFFERENTIAL. Ensure that the

OPERATED
or
LATCHED
PERCENT DIFFERENTIAL
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
S4 ELEMENTS
DIFFERENTIAL
PERCENT
depending on the
S4
PERCENT DIFFERENTIAL
