Determining the Amp/Circuit Requirements

Use the following formula to determine/calculate the amperage/circuit requirements for all devices associated with the press; this
includes the Print Server, OHCF, and optional finishing devices.
 
NOTE:
This formula does not calculate the press since it is on its own dedicated circuit.
 
Determine the amps required for each device.
1.
Calculate the total amp sum of all the devices.
2.
The sum total is:
3.
12 or below; therefore, a 15 amp circuit may be used with NEMA 5-15R. However, a 20 amp circuit is recommended using
NEMA 5-20R receptacles.
12.1 - 16; a 20 amp circuit is required (NEMA 5-20R receptacles).
 
Calculate the total number of devices associated with press, including the Print Server, OHCF, and all optional finishing
4.
devices.
This calculation is number of receptacles required. Refer to the following two examples.

Recommended Wall Receptacle Placement

The recommended wall receptacle placement for the print server, OHCF, the press, and its accessories are shown in the following illustration.
This is for USA receptacles only. It is recommended that receptacles be grouped as shown in relation to the print engine.
 
The following illustration shows a full configuration consisting of a standalone print server, Advanced HCF, the press, Interface Module, GBC
AdvancedPunch Pro, High Capacity Stacker, Booklet Maker Finisher with C/Z Folder, and SquareFold Trimmer Module.

Electrical Installation Considerations

Press Electrical Considerations

Ground Fault Protection is provided which meets Xerox internal safety requirements and exceeds the Industry Standards for
Information Technology Equipment.
The electrical outlet must be located within 6 feet (1.83 m) to the right of the right rear corner of the main processor, or no
more than 3 feet (0.914 m) to the left of the left rear corner of the main processor (when facing the equipment)
The power cord must have sole use of the circuit. The outlet/circuit cannot be shared with any other devices or equipment
OHCF should be placed within 6 feet (1.83 meters) of wall outlets.
OHCF have their own power cord and must be plugged into an outlet separate from the print engine. Ensure that there are
enough wall outlets.
Customer Expectation & Installation Guide
Versant 80 Press