Menu 6:
Maximum temperature set point for the room sensor
Change the temperature value with <
Confirm by pressing <
Menu 7:
Minimum temperature set point for the floor sensor
Change the temperature value with <
Confirm by pressing <
Menu 8:
Maximum temperature set point for the floor sensor
This value is the max. limit value for the floor sensor
in room sensing mode with floor limiter.
Change the temperature value with
<
Confirm by pressing <
34
> buttons.
> button.
Possible values:
from 5°C [5.0] to 40°C [40.0]
(room regulation)
from 5°C [5.0] to 35°C [35.0]
(floor regulation)
Factory value:
40.0°C (room regulation)
35.0°C (floor regulation)
> button.
room regulation mode:
Not possible to set min. floor
temperature limit
room sensing with limiter
floor regulation mode:
Possible values: from 5°C [5.0]
to 15°C [15.0]
Factory value : 5.0°C
> button.
room regulation mode:
Not possible to set max. floor
temperature limit
> buttons
> buttons