Note
Figure 3-3 Settings
DHCP
Note
UDP port
Foreign device
20/70
Siemens
Building Technologies
3.2.1

Language

Select the language here. The basic setting is English.
3.2.2

IP settings (PXM20-E only)

These settings must be carried out only by (or by arrangement with)
your system administrator or network administrator.
Set your network parameters here.
If the dynamic IP configuration in your network is set up via DHCP
(Dynamic Host Configuration Protocol), then the settings for the IP
address, subnet mask and default gateway are provided by the
DHCP server. These settings cannot be modified.
If the IP address, subnet mask and default gateway settings are
entered manually, they are not checked for consistency.
BACnet communicates via UDP (User Datagram Protocol) and IP
(Internet Protocol). The default UDP port for BACnet is BAC0. A port
other than the default UDP port can be set by means of the edit
string.
Figure 3-5 Setting the UDP port
The BBMD (BACnet Broadcast Management Device) function is
required for BACnet communications between the different IP
segments (separated by IP routers). The PXM20-E from another IP
segment can register itself with BBMD as a foreign device. This
PXM20 / PXM20-E operator unit
Settings
Figure 3-4 IP settings
CM110754en_02