Design
D Wiring the Power Supply
Make sure that the Inverter and Noise Filter are grounded together.
• Always connect the power input terminals (R/L1, S/L2, and T/L3) and power supply via a dedicated
Noise Filter.
• Reduce the length of the ground wire as much as possible.
• Locate the Noise Filter as close as possible to the Inverter. Make sure that the cable length between
the Noise Filter and the Inverter does not exceed 40 cm.
• The following Noise Filters are available.
3-phase 200-V AC Noise Filter
Inverter
Model 3G3JV-
A2001/A2002/A2004/A2007
A2015/A2022
A2037
Single-phase 200-V AC Noise Filter
Inverter
Model 3G3JV-
AB001/AB002/AB004
AB007/AB015
3-phase 400-V AC Noise Filter
Inverter
Model 3G3JV-
A4002/A4004
A4007/A4015/A4022
A4037
D Connecting a Motor to the Inverter
• When connecting a motor to the Inverter, be sure to use a cable with a braided shield.
• Reduce the length of the cable as short as possible and ground the shield on the Inverter side as well
as the motor side. Make sure that the cable length between the Inverter and the motor does not exceed
20 m. Furthermore, connect a clamp core (Clamp Filter) close to the output terminals of the Inverter.
Product
Clamp Filter
D Wiring a Control Cable
• Be sure to connect a cable with a braided shield to the control circuit terminals.
• Ground the shield on the Inverter side only.
3-phase 200-V AC Noise Filter (Rasmi)
Model 3G3JV-
PRS2010J
PRS2020J
PRS2030J
Single-phase 200-V Noise Filter (Rasmi)
Model 3G3JV-
PRS1010J
PRS1020J
3-phase 200-V AC Noise Filter (Rasmi)
Model 3G3JV-
PRS3005J
PRS3010J
PRS3020J
Model
2CAT3035-1330
Chapter 2
Rated current (A)
10
16
26
Rated current (A)
10
20
Rated current (A)
5
10
15
Manufacturer
TDK
2-29