Advanced Operation
n75
Low Carrier Frequency at Low Speed
Setting
0, 1
range
Set Values
Value
0
Low carrier frequency at low speed disabled.
1
Low carrier frequency at low speed enabled.
• Normally set n75 to 0.
• When the output frequency is 5 Hz or higher and the output current rate is 110% or less, the carrier
frequency will be automatically reduced to 2.5 kHz with n75 set to 1. If the load is heavy at low speed,
the Inverter will withstand higher overcurrent by suppressing the heat radiation of the Inverter caused
by the carrier frequency.
• This function is enabled with 2, 3, or 4 set in n46 for carrier frequency.
6-4
Unit of
1
setting
Description
Chapter 6
Changes during
No
operation
Default setting
0