5. 1

Introduction

A number of functions within the system are hardware
configurable by DIP switches. However, most functions
are software configurable, using the Configuration
Software.
Note
Refer to the Configuration Software Manual
(9922 141 10381) for details about using the
software.
5.2

Hardware configuration

A complete Plena Voice Alarm System can be hardware
configured using:
The system settings DIP switch (see section 5.3), the
VOX configuration (DIP) switches (see section 5.4.2)
and the master volume control knobs on the rear of
the controller.
The CS configuration DIP switch (see section 5.5) on
the bottom of each call station.
The ID rotary switch and the termination switch on
the rear of each router (see section 5.6).
5.3

System settings DIP switch

The system settings are configured using the system
settings DIP switch on the rear of the controller (see
figure 5.1). By default, all switches are in the OFF
position.

Monitor

APR mode

Supervision

2ch operation
LBB1994
figure 5. 1 : System settings DIP switch
Bosch Security Systems | 2004-06 | 9922 141 10371en
table 5. 1 : System settings DIP switch settings
DIP switch
Monitor
APR mode
Supervision
2ch operation
LBB1994
5.3.1
If the Monitor switch (see figure 5.1) is in the ON
position, the internal monitoring loudspeaker of the
controller is switched on. The volume of the monitoring
loudspeaker is set with the Monitoring Speaker master
volume control knob (see figure 2.3, no. 35).
5.3.2
If the APR mode switch (see figure 5.1) is in the ON
position, the system operates in the Asian-Pacific
Region (APR) mode. In APR mode, the system operates
according to the emergency standards of the Asian-
Pacific Region.
5.3.3
If the Supervision switch (see figure 5.1) is in the ON
position, supervision is enabled. If it is in the OFF
position, supervision is disabled. To indicate that
supervision is disabled, the Disabled indicator on the
front panel of the controller is turned ON (see figure
Off
5.2). For an overview of all functions that can be
supervised, see 5.3.3.1.
On
0 dB
-6dB
-20dB
figure 5.2: Supervision: Disabled indicator
Description
Switches the monitoring
loudspeaker on (ON) or off (OFF).
See section 5.3. 1 .
Switches the Asian Pacific Region
mode on (ON) or off (OFF). See
section 5.3.2.
Switches supervision on (ON) or off
(OFF). See section 5.3.3.
Switches 2-channel operation on
(ON) or off (OFF). See section 5.3.4.
For future use. This switch must
always be in the OFF position.
Monitor
APR mode
Supervision
Fault Indicators
Processor reset
Mains
Network
Battery
Message
Call/EMG
Music/Spare
EMG mic
Ground short
RCP
Input
Router
en | 47
Disabled
A
B
Zone1
Zone2
Zone3
Zone4
Zone5
Zone6