Plena Voice Alarm System | Installation and User Instructions | Installation
4. 1 1

Connecting line output

The voice alarm controller has one line output (see
figure 4.14). This output has a double cinch socket. Both
cinch sockets contain the same, mono signal, which
consists of the current BGM and calls. The line output
can be used to connect the controller to a recording
device (e.g. a tape-deck).
LBB1990/00
Voice Alarm Controller
Booster
figure 4. 1 4: Connecting line output
Bosch Security Systems | 2004-06 | 9922 141 10371en
4. 1 2
The controller has 3 trigger output contacts. The trigger
output contacts (see figure 4.15) can be used to indicate
the current state of the system to third-party equipment,
to trigger particular actions, e.g. activating a signalling
light or a beeper if the system has entered the
emergency state (see section 6.6).
In
CD/Tuner
table 4.8: Trigger outputs
The trigger output contacts are implemented as internal
relays offering a normally closed (NC) and a normally
open (NO) contact. By default, all contacts are de-
energized (NC is connected to COM). On entering one
of the states, as mentioned in table 4.8, the
corresponding output contact is energized (NO is
connected to COM).

Connecting trigger outputs

LBB1990/00
Voice Alarm Controller
Z1
Z2
Z3
Z4
Z5
Z6
TR
figure 4. 1 5: Connecting trigger outputs
Contact
Description
EMG
Emergency state (see also section
4.12.1).
Fault
Fault state (see also section
4.12.2).
Call
Call state (see also section 4.12.3).
en | 40
NC
EMG
COM
NO
NC
Fault
COM
NO
NC
Call
COM
NO
NC
V
olume Overr
24V
NO
TRG2
NC
COM
NO