Chapter 5 Parameter Introductions
P1.06 Time of S-curve initial
P1.07 Time of S-curve rising
Note:
P1.06 and P1.07 are only active when the Acc/Dec mode is S-curve mode (P1.05=1) and
P1.06+P1.07≤90%.
Starting process of S-curve is shown in Fig. 5-1-5 as "①", where the changing rate of
output frequency increases from 0.
Rising process of S-curve is shown in Fig. 5-1-5 as "②", where the changing rate of
output frequency is constant.
Ending process of S-curve is shown in Fig. 5-1-5 as "③", where the changing rate of
output frequency decreases to zero.
 Tips:
S curve Acc/Dec mode is suitable for the conveying load such as elevator and
conveying belt.
P1.08 Stop mode
0: Deceleration to stop
2: Deceleration +DC braking
Note:
0: Dec-to-stop
After receiving the stop command, the inverter reduces its output frequency
within the Dec time, and stops when the frequency decreases to zero.
1: Coast-to-stop
After receiving the stop command, the inverter stops output immediately and the
load stops under the effects of mechanical inertia.
2: Dec-to-stop +DC injection braking
After receiving the stop command, the inverter reduces its output frequency
according to the Dec time and starts DC injection braking when its output
frequency reaches the preset frequency of braking.
Refer to the Notes of P1.09~P1.12 for the functions of DC injection braking.
P1.09 DC injection braking frequency at
stop
P1.10 DC injection braking waiting time
at stop
90
Range: 10.0~50.0%【20.0%】
Range: 10.0~80.0%【60.0%】
Range: 0~2【0】
1: Coast to stop
Range: 0~MIN (50.00, Frequency upper
limit) 【0.00Hz】
Range: 0.00~10.00s【0.00s】