Chapter 5 Parameter Introductions
Setting
Function
Preset operating
15
time arriving out
Torque arriving
detection
16
threshold
CL: Current
17
Limiting
Over-voltage stall
18
Inverter fails
19
External fault stop
20
(EXT)
Uu1: Under
21
voltage lock-up
Reserved
22
OLP2: Overload
23
signal
Analog signals 1
24
abnormal
Analog signals 2
25
abnormal
STEP: Program
26
Running steps
Fault type output
27
Fixed-length
28
arriving
Standby
29
30
Zero-speed
114
When the total operating time (PE.09) reaches the
preset operating time (P3.26), the output of terminal is
valid.
If motor's torque is reach reference value (set by
P3.23), the output of terminal is valid.
If it is lower than 80% of reference value, the terminal
is invalid.
If output current is reach current amplitude limiting
level (set by Pd.05), the output of terminal is valid.
If it is lower than 80%, the output of terminal is invalid.
If motor's torque is reach over voltage point at stall (set
by Pd.07), t the output of terminal is valid.
If it is lower than 80%, the output of terminal is invalid.
If the inverter has fault, the output of terminal is
invalid.
If the inverter halt is caused by external fault, the output
of terminal is valid.
If the DC bus voltage is lower than the voltage lower
limit, the output of terminal is valid.
Reserved
If the output current is higher than the value defined by
Pd.02 (Overload detection), the output of terminal is
valid.
If analog signal 1 level is lower than the minimum
signal and lasts 500 ms, the output of terminal is valid.
If analog signal 2 level is lower than the minimum
signal and lasts 500 ms, the output of terminal is valid.
Running steps of instruction program and the
corresponding procedure, and outputs, refer to Table
5-3-4. , the output of terminal is valid for models
3004GB/35R5PB and below .
See Table 5-3-4 for faults that correspond to the output
signal. The function of terminal is reserved for models
3004GB/35R5PB and below .
If the actual length defined by P8.01 is longer than the
length defined by P8.00, the output of terminal is valid.
If the inverter is in standby state, the output of terminal
is valid.
If output frequency is zero, the output of terminal is
valid.
Description