Chapter 5 Parameter Introductions
PE.11 Total electric-consumption (MWh)
PE.12 Total electric-consumption (KWh)
Note:
"Total Operating time" (PE.09) records the actual operating time from first use of
the inverter to present.
"Total Power On time" records the actual time that the inverter is power-on from
first power on to present.
"Total electric-consumption (MWh)" records the high 16 bits of inverter's total
electric--consumption.
"Total electric-consumption (KWh)" records the low 16 bits of inverter's total
electric--consumption.

5.16 Protection of Parameters (Group PF)

PF.00 User password
Note:
User password setting: The initial value of user password is 0, which means the
password protection function is invalid. At this state, user can access all parameters
and parameters content of Group PF.
Unlock the user password: If the user password is effective, the preset password is
required to access Group PF. Otherwise, no parameters of Group PF can be
accessed.
Changing the user password: If password protection function is effective, right
password must be input first to unlock. After unlocking, select PF.00, re-change
this parameter value, and press "ENTER" to save the value. Now, the password
changing is completed. Before changing the user password, remember to set PF.01
to 0, so that all parameters are allowed to be changed.
 Tips:
The password will become effective when you press "PRG/ESC" to exit from Group
PF if you set user password.
Please remember the password, otherwise, you will have no access to all parameters of
Group PF.
If you forget user password, please contact with manufacturer,
Example: Set the password to 1234, then exit from Group PF and unlock the user
password. The process is shown in Fig. 5-15-1 and Fig. 5-15-2.
PF.01 Parameter write-in protection
0: All parameters can be changed;
1: Only setting frequency (P0.00) and PF.01 can be changed;
2: Only PF.01 can be changed.
Note:
PF.01 is set to 0: All parameters are allowed to be changed But only the parameters,
which are marked "○" in function table, can be changed no matter what the inverter
160
Range: 0~9999MWh【0】
Range: 0~999KWh【0】
Range: 0~9999【0】
Range: 0~2【0】