Appendix 4 MODBUS Communication
● Data List:
●Command data (Only write-in is possible)
Address
Name
0000H
Run
0001H
Operation
Signal
Frequency
0002H
Reference
0003H
0004H
0005-001FH
*NOTE 1: Reserved BIT always writes "0".
*NOTE 2: If communication frequency reference is more than the maximum frequency,
the communication instruction will not be accept by the inverter.
208
BIT
(Reserved)
0
Run command (1: Run 0: Stop)
1
Reverse command (1: REV 0: FWD)
2
External fault (1: External fault [EF0])
3
Fault reset (1: Fault reset)
Multi-function reference 1 (P3.01 X1 Terminal
4
function)
Multi-function reference 2 (P3.02 X2 Terminal
5
function)
Multi-function reference 3 (P3.03 X3 Terminal
6
function)
Multi-function reference 4 (P3.04 X4 Terminal
7
function)
Multi-function reference 5 (P3.05 X5 Terminal
8
function)
Multi-function reference 6 (P3.06 X6 Terminal
9
function)( Only 35R5GB/37R5PB ~ 3500G)
Multi-function reference 7 (P3.07 X7 Terminal
A
function) ( Only 35R5GB/37R5PB ~ 3500G)
Multi-function reference 8 (P3.08 X8 Terminal
B
function) (Only 35R5GB/37R5PB ~ 3500G)
C-F
(Reserved) *NOTE 1
The unit is selected by the constant Pb.04
Communication PID feedback,
Data range 0-1000 corresponding to 0.0~100.0%.
Set PC.15 value to 1 for monitoring PID feedback by
keyboard
Communication PID feed,
Data range 0-1000 corresponding to 0.0~100.0%.
Set PC.16 value to 1 for watching PID feed by keyboard
(Reserved)
Descriptions
*NOTE 2