Chapter 5 Parameter Introductions
details.
P0.03 Frequency setting selection
0: Frequency setting 1
1: Terminal Selection
2: Frequency setting 1+ Frequency setting 2
3: | Frequency setting 1- Frequency setting 2 |
4: Min(Frequency setting 1, Frequency setting 2)
5: Max(Frequency setting 1, Frequency setting 2)
Note:
Frequency settings 1: Frequency set by P0.01 (Frequency setting 1).
Terminal Selection: If defined the "FC" function terminals (see P3.01 ~ P3.08), and
the terminal function is effective, P0.02 (frequency setting 2) will be selected as the
final frequency setting ; if defined this function terminal but the terminal function is
not effective, P0.01 (frequency setting 1) will be selected. If undefined the "FC"
function terminal, P0.01 (frequency setting 1) will be the default frequency setting.
Frequency setting selection can be switched between the two different signals.
Settings 2 to 5: The final reference frequency value will be decided by frequency
setting 1 and frequency setting 2 after the corresponding arithmetic.
Additional Note:
If P0.01 is set to 7(UP / DOWN) or 10 (wobble frequency operating), setting value 3 to
5 of P0.03 (P0.03=3~5) will be invalid, and setting value 0 will be valid. See terminal
UP / DOWN function definition in parameter group P3 and wobble frequency
operating definition in parameter group P6 for details.
If P0.01 select 9(PID closed loop) and P0.03 is configured to combined
frequency(P0.03>1), multiplexing parameter P2.11 is used to define the analog PID
regulator's output frequency limit and the frequency range is -P2.11~ P2.11(Unit Hz).
P0.04 Run command mode selection
0: Keyboard control
1: Terminal control 1 (STOP invalid)
2: Terminal control 2 (STOP valid)
3: Serial communication 1 (STOP invalid)
4: Serial communication 2 (STOP valid)
5: Terminal control 3 (STOP and JOG invalid)
Note 1:
Keyboard control: Control the inverter Start and Stop by pressing the "RUN" key
and "STOP/RESET " key on the keyboard.
80
Range: 0~5【0】
Range: 0~5【0】