System Power Off Illustration; Running History Record (Group Pe); Machine Does Not Shut Down After Power Failure - Alpha 6000 User Manual

Table of Contents

Advertisement

Chapter 5 Parameter Introductions

System power off illustration

Output Freq. (Hz)
Reference
Freq.
Power on, Run
Fig. 5-13-7 Machine does not shut down after power failure

5.15 Running History Record (Group PE)

PE.00 Type of latest fault
PE.01 Output frequency at last fault
PE.02 Reference frequency at last fault
PE.03 Output current at last fault
PE.04 DC bus voltage at last fault
Note:
If faults occur during operating, the inverter stops PWM output immediately, and
accesses to the fault protective state. Moreover, the fault indicator "TRIP" is lit up
and flickered. The operating condition (such as output frequency, reference
frequency, output current, and DC bus voltage etc.) of latest fault and types of the
last 3 faults, could see in PE.01~PE.08. Descriptions of faults are shown in Table
5-14-1:
Fault
Fault categories
code
No fault
NULL
Uu2
Control circuit Under voltage Uu3
OC1
Over current in Acc process
158
Power off
Range: Table 5-14-1【NULL】
Range: 0~Frequency upper limit【0.00Hz】
Range: 0~Frequency upper limit【0.00Hz】
Range: 0~2 times of rated current【0.0A】
Range: 0~1000V【0V】
Table 5-14-1 Fault categories
Fault
code
Uu1
OC2
Fault categories
Bus Under voltage
Charging circuit is in poor
condition
Over current in Dec process
Time (s)
Power on

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6100

Table of Contents