Saia-Burgess Controls AG
for over 20 seconds, parameter node will be terminated and the current setting will
become active.
Wireless signals are carried across zones and through walls. This makes it necessary
to match the wireless transmitter uniquely to the receiver connected directly to the
room controller with the PCD7.L670 connecting cable. A commissioning procedure is
run to match the mobile room control unit to the desired receiver.
Function
Matching of control unit to
receiver
Battery test
Receiver number
Manual for PCD7.L6xx room operator units  │   D ocument 26-859  ENG07  │   2 015-06-04
Description
The room controller and receiver must be powered on and
in operation..
Press the function keys
The display shows the currently configured receiver ad-
dress and the bar graph flashes as long
as the room control unit is ready to be given a new
receiver address.
The receiver transmits its ID when the small button on the
back of the device next to the cable inlet is pressed; this is
accessible after removing the base of the housing.
When the ID has been received successfully, the bar
graph on the display stops flashing and the new receiver
address is displayed and saved permanently.
Pressing any of the function keys will cancel the procedure
and the old receiver address will be retained.
This procedure can be repeated in the same way anynum-
ber of times.
The
key is used to run the integrated test function.
All the display symbols flash and the charge level of the
battery is displayed; BAT.ON stands for sufficient capac-
ity, but when BAT.OFF is displayed, the battery should be
changed.
This parameter is reserved for future developments and
must be set to 0 for compatibility with the PCD7.L60x
system.
To activate the address setting, the function keys
and
must be pressed together for at least 1 second.
The display then shows the currently configured address.
The
and
keys can be used to modify the address
in the range from 0...4.
Factory setting: 1
Digital room controller units
,
, and
together.
3
,
3-20