10. Please note the following diagram. The diagrams show the ceiling and wall mounting of the HEAT-
SCOPE™ including all minimum clearances to be observed. The prescribed minimum mounting height
of the HEATSCOPE™ radiant heater is 82,7 inch / 210 cm.
11. The assembled units must have a clearance of at least 59 inch / 150 cm to each other on the longer
side. If the devices are mounted with the heating surfaces aligned to each other, they must have a
clearance of at least 118 inch / 300 cm.
Minimum clearances
The dimensions given are minimum values and may differ from the local building and fire regulations.
The latter must be observed and complied with in any case.
The illustrated installation surfaces must comply at least with fire protection class A2.
Please note: The HEATSCOPE™ fulfills IP protection class 4 (IP-X4) for ceiling mounting and IP protection
class 0 (IP-X0) for wall mounting.
A
> 12 inch/30cm to the wall
> 3 inch/6 cm to another HEATSCOPE™
B
> 12 inch/30 cm to the wall
> 60 inch/150 cm to another HEATSCOPE™
C
> 3 inch/6 cm
D
> 12 inch/30 cm to the wall
> 3 inch/6 cm to another HEATSCOPE™
Protect from
wind and drafts.
E
> 83 inch/210 cm
F
> 32 inch/80 cm
G
> 8 inch/20 cm
H
> 5 inch/12 cm
I
> 83 inch/210 cm
J
> 3 inch/6 cm
Protect from moisture
and humidity.
K
> 12 inch/30cm to the wall
> 59 inch/150 cm to another HEATSCOPE™
L
> 83 inch / 210 cm