Starting The Ups (Normal); Stopping The Ups - Toshiba 1600XP SERIES Installation And Operation Manual

Hide thumbs Also See for 1600XP SERIES:
Table of Contents

Advertisement

Parameter
526
# External Batt. Strings in Parallel
527
External Battery Capacity in A-hr
1 These settings apply to 1600XP/1600XPi Non-matching battery cabinets.
2 Battery runtimes on the UPS display will not be accurate when using a non-Toshiba external battery
cabinet.

11.3 Starting the UPS (Normal)

Turn the main circuit breaker (MCCB) on the back of the UPS (see
breaker should remain in the ON position.
Verify that the On-Line LED on the front panel (see
The UPS will now be supplying power in the On-Line mode. If the On-Line LED is not illuminated push and
hold the RUN key for approximately 3 seconds.
When running the UPS for the first time charge the batteries for at least 24
hours (input breaker on) before operating the connected load. Failure to do so
will result in reduced battery backup time.

11.4 Stopping the UPS

To stop the UPS press and hold the STOP key approximately 3 seconds until the On-Line LED changes
from green to off (audible beep). The UPS is now in the bypass mode.
If the input breaker is turned off while UPS is in the bypass mode, the output
power stops. Any load devices will lose power.
Ensure that all sensitive loads have been previously shut down.
To completely stop the UPS, turn the input breaker at the back of the UPS to the OFF position.
1600XP/XPi Series Installation and Operation Manual – 60616-012
Description
"12.1 Front Panel Layout" on page
NOTICE
NOTICE
UPS
UPS
UPS +
Size
Only
3.6 kVA
0
6 kVA
0
8-22 kVA
0
All
0
Appendix
A) to the ON position. The
UPS +
1 BC
2 BC
1
1
1
1
1
1
1
1
9
9
24) lights green.
23