Toshiba 1600XP SERIES Installation And Operation Manual page 120

Hide thumbs Also See for 1600XP SERIES:
Table of Contents

Advertisement

UPS
ESTIMATED
RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating
PF
Output
Voltage
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 1 MATCHING BATTERY CABINET @ .85pf
Rating
PF
Output
Voltage
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
UPS
ESTIMATED
RUNTIME WITH INTERNAL BATTERIES AND 2 MATCHING BATTERY CABINETS @ .85pf
Rating
PF
Output
Voltage
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
6
0.85
240
D4
Rated I
Rated
Output
Load %
Watts
25.00
0.10
510
25.00
0.20
1020
25.00
0.30
1530
25.00
0.40
2040
25.00
0.50
2550
25.00
0.60
3060
25.00
0.70
3570
25.00
0.80
4080
25.00
0.90
4590
25.00
1.00
5100
Rated I
Rated
Output
Load %
Watts
25.00
0.10
510
25.00
0.20
1020
25.00
0.30
1530
25.00
0.40
2040
25.00
0.50
2550
25.00
0.60
3060
25.00
0.70
3570
25.00
0.80
4080
25.00
0.90
4590
25.00
1.00
5100
Rated I
Rated
Output
Load %
Watts
25.00
0.10
510
25.00
0.20
1020
25.00
0.30
1530
25.00
0.40
2040
25.00
0.50
2550
25.00
0.60
3060
25.00
0.70
3570
25.00
0.80
4080
25.00
0.90
4590
25.00
1.00
5100
1600XP/XPi Series Installation and Operation Manual – 60616-012
# Batt
# Strings
Nominal
18
1
216
18
1
216
18
1
216
18
1
216
18
1
216
18
1
216
18
1
216
18
1
216
18
1
216
18
1
216
# Batt
# Strings
Nominal
18
3
216
18
3
216
18
3
216
18
3
216
18
3
216
18
3
216
18
3
216
18
3
216
18
3
216
18
3
216
# Batt
# Strings
Nominal
18
5
216
18
5
216
18
5
216
18
5
216
18
5
216
18
5
216
18
5
216
18
5
216
18
5
216
18
5
216
Runtime
82
48
32
22
16
13
11
9
8
7
Runtime
180
120
90
72
60
51
45
40
35
30
Runtime
300
180
135
112
90
82
70
63
55
51

Hide quick links: