Toshiba 1600XP SERIES Installation And Operation Manual page 80

Hide thumbs Also See for 1600XP SERIES:
Table of Contents

Advertisement

Capacity
Power Connections
Emergency Power Off
Remote Contacts
RS232 ASCII Interface
RemotEye 4
(Standard with XPi)
(Optional with XP)
Mechanical Design
Enclosure
Size (HxWxD) (max)
Paint System
Fan Panel
Battery System
Battery Replacement
Battery Packs
Battery Pack Size (HxWxD) max.
Battery Pack Quantity
Battery Manufacturer
Battery Type
Toshiba Part Number for Battery
Pack
1.
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
Derate to 18.7 kVA (15.9 kW) for 50 Hz operation.
A6
STANDARD MODELS: 14 – 22 KVA (CONT'D)
14 kVA (11.9 kW)
1
Standard – Terminal contacts only
Standard (INV, BYP, BATT, LB, AC, FLT)
Toshiba UPS Communication Protocol 2.0
Remote communications package (HTTP/HTTPS, SNMP, Modbus TCP/RTU,
BACnet IP/MSTP) via RJ-45 or RS-485
Enclosure of unit made from sheet metal meeting NEMA1 and UL
Panel mounted on back of UPS to allow for
Slide out battery packs accessible from front of UPS,
factory or authorized service center serviceable only
Designed for battery acid leakage containment with (6) batteries per pack
51896-FS
1600XP/XPi Series Installation and Operation Manual – 60616-012
18 kVA (15.3 kW)
22 kVA (18.7 kW)
1
Standard – Hard wire
39.0 x 17.5 x 36.1 in.
(991 x 445 x 917 mm)
Powder coating
easy replacement of fans
5.0 x 7.3 x 19.0 in.
(127 x 185 x 462 mm)
8
YUASA
REW45-12FR
1, 5
60995-FS

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1600xpi series

Table of Contents