System Fault Messages - Toshiba 1600XP SERIES Installation And Operation Manual

Hide thumbs Also See for 1600XP SERIES:
Table of Contents

Advertisement

23.3 System Fault Messages

A Fault message is generated when either a fault condition occurs, or a warning condition occurs three
times within ten minutes. The table below shows the possible fault messages and what actions need be
taken.
If the input voltage is normal when the fault occurs then the UPS will switch immediately to the bypass mode
to continuously feed power to the load.
If the fault condition occurs while the input power is abnormal and the UPS is in Bypass mode the UPS will
shut down the output to prevent load equipment damage.
When a Fault condition exists, the red LED on the UPS display panel will illuminate until the fault is cleared.
All faults are recorded. The fault status can cleared by cycling power (turn off, then turn on) after the prob-
lem has been fixed.
Display
Recorded
BYPOH
Y
Bypass Overheat – Overheating
condition occurred.
BYPOL
Y
Bypass Overload – UPS is over-
loaded.
CHRGOV
Y
Charger Overvoltage – Charger
overvoltage condition occurred.
CLMT
Y
Current Limit – Load on UPS out-
put exceeds unit specifications.
DCIB
Y
DC Bus Imbalance – DC voltage
imbalance occurred.
DCOC
Y
DC Bus Overcurrent – DC overcur-
rent condition occurred.
DCOV
Y
DC Bus Overvoltage – DC over-
voltage condition occurred.
DCUVBS
Y
DC Bus Undervoltage during
Boostup Mode – DC Bus under-
voltage condition occurred.
DCUVC
Y
DC Bus Undervoltage During
Charging Mode – DC Bus under-
voltage condition occurred.
DVCOH
Y
Device Overheat – Overheating
condition occurred.
1.
EXTBC1
N
2.
3.
1600XP/XPi Series Installation and Operation Manual – 60616-012
Meaning
BC1 Battery String 1, 2, or 3
Loose HCT Connection
BC1 Over Voltage Fault
BC1 Over Current Fault
Action
Check unit for blocked or in-operable fan. Lower
ambient temperature if it is greater than 104 °F (40
°C). Bypass operation will also cease if overheat
condition is not corrected within 1 hr. of inverter
shutdown. Try restarting. If condition reoccurs plan
for total shutdown and call for service.
Shut down excess equipment to reduce load.
UPS is faulty. Check the UPS operation conditions
at time of fault. Not advisable to restart the UPS.
Call Toshiba for service.
Reduce load on UPS output.
Possible causes are UPS fault are connection of
half-wave rectifier load. Check load and try restart-
ing. If condition persists,call Toshiba for service.
UPS is faulty. Check the UPS operation conditions
at time of fault. Not advisable to restart the UPS.
Call Toshiba for service.
UPS is faulty, input wiring error, input overvoltage
or connection of a motor load. Try restarting. If con-
dition persists call Toshiba for service.
UPS is faulty. Check the UPS operation conditions
at time of fault. Not advisable to restart the UPS.
Call Toshiba for service.
UPS is faulty. Check the UPS operation conditions
at time of fault. Not advisable to restart the UPS.
Call Toshiba for service.
Reduce equipment load to 100% or less and try
restarting.
Call Toshiba for Service.
Call Toshiba for Service
Call Toshiba for Service
53

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1600xpi series

Table of Contents