Manual Run/Stop Operation

Starting the UPS

Turn the main circuit breaker (MCCB) on the back of the UPS (see pages 45-46) to the "on"
position (the breaker should normally remain in the "on" position).
Check that the
All LED's on the front panel may light for a moment when the input breaker is turned "on". This
is normal. The UPS will now be supplying power in the bypass mode.
CAUTION
Press
to begin UPS operation (see page 29 for startup screens).
Run

Stopping the UPS

To stop the UPS, press the
from green to "off". The UPS is now in the bypass mode.
To completely stop the UPS, turn the input breaker at the back of the UPS to the "off" position.
CAUTION
TOSHIBA
LED on the front panel (see page 27 and 28) lights 'green'.
Note: When running the UPS for the first time or after
the power failure backup operation, charge the
batteries for at least 24 hours (input breaker "on")
before operating the connecting
load. Using the UPS without charging the battery
shortens the battery backup operation time, which
could result in the destruction of data in case of a
power failure.
Stop
key approximately 1 second until the
Note: If the input breaker is turned off while UPS is in the
bypass state, the output power stops. Any load devices
will lose power. Ensure that all sensitive loads have been
previously shut down.
42