Fireplace hearth requirements: (Measured without the insert)
The non-combustible fi replace hearth must be raised 2" above an adjacent combustible fl oor and extend 16" in front and
8" beyond each side of the existing fi replace opening. A non-combustible hearth that extends a minimum 23-1/2" in front
of the fi replace opening may be fl ush to an adjacent combustible fl oor.
MINIMUM FIREPLACE
OPENING AND HEARTH
DIMENSIONS
21"
8"
Ember protection:
**
Combustible fl oor in front of the fi replace insert must be protected from hot embers by non-combustible material extend-
ing 16" to the fi ring side and 8" to other sides of the unit.
Consult CAN/CSA-B365 Installation Code for Solid-Fuel-Burning appliances and equipment in Canada, and N.F.P.A.
211 Standard for chimneys, fi replaces, vents and Solid-Fuel-Burning appliances in USA.
MINIMUM EMBER
PROTECTION
DIMENSIONS
Non-combustible fi replace
hearth
Non-combustible fl oor
covering
ALT5.CPINSB 080515-24
24 1/2"
24"
Non-combustible fi replace
18 1/4"
8"
*
2"
23 1/2"
**
18"
16"
hearth
2"
©PACIFIC ENERGY FIREPLACE
PRODUCTS LTD.
18"
2"
5