Installing The Oil Supply As A Single Line System - Viessmann VITOLADENS 300-W Installation And Service Instructions Manual

Wall mounted oil condensing boiler
Table of Contents

Advertisement

Installation sequence

Installing the oil supply as a single line system

A
A Fuel oil filter with automatic air vent
valve
Install a single line fuel oil filter R ⅜ (filter
grade max. 40 µm) and a fuel oil air vent
valve in the oil supply.
We recommend:
■ Automatic fuel oil air vent valve with
filter: FloCo-Optimum-K (filter grade
5 µm).
■ For replacement during maintenance:
Oil filter element Microtec MC-18 (filter
grade 5 µm).
See Vitoset pricelist.
For tanks below the oil burner pump:
If the suction head or the max. pipe
length is greater than specified in the fol-
lowing table, install an oil feed pump with
intermediate tank in the immediate prox-
imity of the boiler.
12
B
B Foot valve
Sizing the oil line
Suction
Max. pipe length in m with
head H
suction line internal diam-
in m
eter
4 mm
+4.0
100
+3.5
95
+3.0
89
+2.5
83
+2.0
77
+1.5
71
+1.0
64
+0.5
58
0.0
52
-0.5
46
-1.0
40
-1.5
33
-2.0
27
-2.5
21
-3.0
15
-3.5
-4.0
5 mm
6 mm
100
100
100
100
100
100
100
100
100
100
97
81
66
51
36
9
21
6
100
100
100
100
100
100
100
100
100
100
100
100
100
100
75
44
12

Advertisement

Table of Contents
loading