Viessmann VITOLADENS 300-W Installation And Service Instructions Manual page 79

Wall mounted oil condensing boiler
Table of Contents

Advertisement

Solar
(cont.)
Coding in the delivered condition
0A:5
Temperature differential
for stagnation time reduc-
tion (reduction in the
speed of the solar circuit
pump to protect system
components and heat
transfer medium) 5 K
0b:0
Frost protection function
for solar circuit switched
off
0C:1
Delta T monitoring
switched on.
No flow rate captured in
the solar circuit, or flow
rate too low
0d:1
Night circulation monitor-
ing switched on.
Unintentional flow rate is
captured in the solar cir-
cuit (e.g. at night).
0E:1
Heat statement in con-
junction with Viessmann
heat transfer medium.
0F:70
Flow rate solar circuit at
max. pump speed
7 l/min.
10:0
Target temperature con-
trol switched off (see cod-
ing address "11").
11:50
Set solar DHW tempera-
ture 50 °C.
Possible change
0A:0
Stagnation time reduction
is disabled
0A:1
Temperature differential
to
adjustable from 1 to 40 K
0A:40
0b:1
Frost protection function
for solar circuit switched on
(not required with
Viessmann heat transfer
medium)
0C:0
Delta T monitoring switch-
ed off.
0d:0
Night circulation monitor-
ing switched off.
0E:2
Do not adjust
0E:0
No heat statement.
0F:1
Flow rate adjustable from
to
0.1 to 25.5 l/min.
1 step ≙ 0.1 l/min
0F:255
10:1
Target temperature control
switched on.
11:10
The set solar DHW temper-
to
ature is adjustable from 10
11:90
to 90 °C.
Code 2
79