Viessmann VITOLADENS 300-W Installation And Service Instructions Manual page 70

Wall mounted oil condensing boiler
Table of Contents

Advertisement

Code 2
General
(cont.)
Coding in the delivered condition
3d:5
DHW circulation pump
runtime for brief opera-
tion: 5 min
3E:0
Internal circulation pump
stays in control mode at
signal "External block-
ing"
3F:0
Internal circulation pump
stays in control mode at
signal "External de-
mand"
70
Possible change
3C:2
Function input DE3: Exter-
nal demand with set flow
temperature.
Flow temperature setting:
Coding address 9b.
Internal circulation pump
function: Coding address
3F
3C:3
Function input DE3: Exter-
nal blocking.
Internal circulation pump
function: Coding address
3E
3C:4
Function input DE3: Exter-
nal blocking with fault mes-
sage input
Internal circulation pump
function: Coding address
3E
3C:5
Function input DE3: Fault
message input
3C:6
Function input DE3: Brief
operation, DHW circulation
pump (pushbutton func-
tion).
DHW circulation pump run-
time adjustment: Coding
address 3d
3d:1
DHW circulation pump run-
to
time adjustable from 1 to
3d:60
60 min
3E:1
Internal circulation pump
stops at signal "External
blocking"
3E:2
Internal circulation pump
starts at signal "External
blocking"
3F:1
Internal circulation pump
stops at signal "External
demand"