Fault codes
(cont.)
Displayed
System characteris-
fault code
tics
Fb
Burner in a fault
state
Fd
Burner in a fault state
and additional fault
b7 is displayed
Fd
Burner blocked
FE
Burner blocked or in a
fault state
FF
Burner blocked
Cause
3 x flame blow-off
during operation
Boiler coding card
is missing
Fault, burner con-
trol unit
Boiler coding card
or main PCB faulty,
or incorrect boiler
coding card
Internal fault
Troubleshooting
Measures
Check oil supply, check
nozzle.
Press reset button R.
Insert the boiler coding
card.
Press reset button R.
Replace control unit if
fault persists
Press reset button R. Re-
place control unit if the
fault persists.
Press reset button R. If
the fault persists, check
the boiler coding card and
replace boiler coding card
or control unit if necessa-
ry
Start the appliance again.
Replace the control unit if
the appliance will not re-
start