Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Economy function room temperature
b5:0
With remote control: no
room temperature-de-
pendent heating circuit
pump logic function
(change code only for
heating circuit with mix-
er)
Parameter ad-
With heating circuit pump logic function:
dress b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
Min. flow temperature heating circuit
C5:20
Electronic minimum flow
temperature limit 20 °C
Max. flow temperature heating circuit
C6:74
Electronic maximum flow
temperature limit set to
74 °C
Heating program - changeover
d5:0
External operating pro-
gram changeover
changes to "Constant op-
eration with reduced
room temperature" or
"Standby mode"
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
> RT
actual
set
> RT
- 1 K
actual
set
> RT
- 2 K
actual
set
(cont.)
Possible change
b5:1
For heating circuit pump
to
logic function, see the fol-
b5:8
lowing table:
Heating circuit pump "ON"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
Possible change
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
boiler-specific parameters)
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by boiler-specific parame-
ters)
d5:1
The external operating pro-
gram changeover switches
to "Constant operation with
standard room tempera-
ture" (subject to coding ad-
dress 3A, 3b and 3C)
Code 1
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
- 1 K
set
- 2 K
set
- 3 K
set
63