Viessmann VITOLADENS 300-W Installation And Service Instructions Manual page 77

Wall mounted oil condensing boiler
Table of Contents

Advertisement

DHW
(cont.)
Coding in the delivered condition
62:2
Circulation pump with
2 min run-on time after
cylinder heating
65:...
Information on the type of
diverter valve (never ad-
just; specified by the boil-
er coding card)
67:40
For solar DHW heating:
Set DHW temperature
40 °C. Reheating is sup-
pressed above the selec-
ted set temperature.
6C:100
Set speed, internal circu-
lation pump for DHW
heating 100 %
6F:...
Max. heating output for
DHW heating in %, speci-
fied by the boiler coding
card
71:0
DHW circulation pump:
"ON" according to time
program
72:0
DHW circulation pump:
"ON" according to time
program
73:0
DHW circulation pump:
"ON" according to time
program
Possible change
62:0
Circulation pump without
run-on time
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
67:0
Set DHW temperature ad-
to
justable from 0 to 95 °C
67:95
(limited by boiler-specific
parameters).
6C:0
Set speed adjustable from
to
0 to 100 %
6C:100
6F:0
Max. heating output for
to
DHW heating adjustable
6F:100
from min. heating output to
100 %
71:1
"OFF" during DHW heating
to set value 1
71:2
"ON" during DHW heating
to set value 1
72:1
"OFF" during DHW heating
to set value 2
72:2
"ON" during DHW heating
to set value 2
73:1
"ON" from once per hour
to
for 5 min up to 6 times per
73:6
hour for 5 min during the
time program
73:7
Constantly "ON"
Code 2
77