Viessmann VITOLADENS 300-W Installation And Service Instructions Manual page 72

Wall mounted oil condensing boiler
Table of Contents

Advertisement

Code 2
General
(cont.)
Coding in the delivered condition
76:0
Without LON communi-
cation module
77:1
LON subscriber number
79:1
With LON communication
module: Control unit is
fault manager
7b:1
With LON communication
module: Control unit
transmits the time
7F:1
Detached house
80:6
If a fault occurs for at least
30 s, a fault message is
displayed
81:1
Automatic summer/win-
tertime changeover
88:0
Temperature displayed in
°C (Celsius)
72
Possible change
76:1
With LON communication
module (automatic recog-
nition)
77:2
LON subscriber number,
to
adjustable from 1 to 99:
77:99
1 - 4 = Boiler
5 = Cascade
10 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Note
Allocate each number only
once.
79:0
Control unit is not fault
manager
7b:0
Does not transmit time
7F:0
Apartment building.
Separate adjustment of
holiday program and time
program for DHW heating
possible
80:0
Immediate fault message
80:2
Minimum fault duration un-
to
til fault message occurs,
80:199
adjustable from 10 s to
995 s; 1 step ≙ 5 s
81:0
Manual summer/winter-
time changeover
81:2
Use of the radio clock re-
ceiver (automatic recogni-
tion)
81:3
With LON communication
module: The control unit re-
ceives the time
88:1
Temperature displayed in
°F (Fahrenheit)