Further details regarding the individual steps

Adjusting the oil pressure and checking the vacuum

Danfoss oil pump, type BFP 52
Suntec oil pump, type ATE2
Commissioning, inspection, maintenance
1. Insert the pressure gauge (measur-
ing range 0 - 25 bar or 0 - 2.5 MPa)
into test port "P" A and the vacuum
A
gauge (measuring range 0 - 1 bar or
0.1 MPa) into test port "V" B.
B
C
Note
D
Seal in the pressure and vacuum
gauges only with copper or alumi-
nium gaskets or with O-rings. Never
use tape to seal these joints.
2. Start the boiler.
3. Set burner stage 1 (see page 34).
4. Where the vacuum measures higher
than 0.35 bar (35 kPa), check the fil-
ter for contamination and check the
pipe route.
5. If required, adjust the oil pressure for
stage 1 at pressure adjusting screw
C of the oil pump (for standard val-
ues, see page 31).
6. Check the actual emission values
after adjusting the oil pressure.
7. Set burner stage 2 (see page 34).
8. If required, adjust the oil pressure for
stage 2 at pressure adjusting screw
D of the oil pump.
9. Check the actual emission values
after adjusting the oil pressure.
(cont.)
33