Viessmann VITOLADENS 300-W Installation And Service Instructions Manual page 75

Wall mounted oil condensing boiler
Table of Contents

Advertisement

Boiler
(cont.)
Coding in the delivered condition
24:0
"Service" not shown on
display
26:0
Burner fuel consumption
(stage 1); no count if
"26:0" is programmed
29:0
Burner fuel consumption
(stage 1 and 2); no count
if "29:0" is programmed
2E:0
Do not adjust
2F:0
Venting program/fill pro-
gram disabled
30:1
Internal variable speed
circulation pump (auto-
matic adjustment)
31:...
Set speed in % of the in-
ternal circulation pump
when operated as boiler
circuit pump, specified by
the boiler coding card
38:0
Status burner control unit:
Operational (no fault)
Possible change
24:1
"Service" is shown on dis-
play (the address is auto-
matically set and must be
manually reset after a serv-
ice has been carried out)
26:1
Entry of 0.1 to 25.5; 1 step
≙ 0.1 litres or gallons/hour
to
26:255
29:1
Entry of 0.1 to 25.5; 1 step
≙ 0.1 litres or gallons/hour
to
29:255
2F:1
Venting program enabled
2F:2
Fill program enabled
30:0
Internal circulation pump
without variable speed
(e.g. temporarily for serv-
ice)
31:0
Set speed adjustable from
to
0 to 100 %
31:100
38:≠0
Status burner control unit:
Error
Code 2
75