Viessmann VITOLADENS 300-W Installation And Service Instructions Manual page 89

Wall mounted oil condensing boiler
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
F8:-5
Temperature limit for ter-
minating the reduced
mode -5 ºC, see example
on page 124.
Observe the setting of
coding address "A3"
F9:-14
Temperature limit for rais-
ing the reduced set room
temperature -14 ºC, see
example on page 124.
FA:20
Raising the set boiler wa-
ter or flow temperature by
20 % when changing
from operation with re-
duced room temperature
to operation with stand-
ard room temperature.
See example on
page 125.
Fb:30
Duration for raising the
set boiler water tempera-
ture or set flow tempera-
ture (see coding address
"FA") 60 min. See exam-
ple on page 125.
(cont.)
Possible change
F8:+10
Temperature limit adjusta-
to
ble from
F8:-60
+10 to -60 °C
F8:-61
Function disabled
F9:+10
Temperature limit for rais-
to
ing the set room tempera-
F9:-60
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
FA:0
Temperature rise adjusta-
to
ble from 0 to 50 %
FA:50
Fb:0
Duration adjustable from 0
to
to 300 min;
(1 step ≙ 2 min)
Fb:150
Code 2
89