Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Party mode time limit
F2:8
Time limit for party mode
or external operating pro-
gram changeover via but-
ton: 8 h
Start temperature raising
F8:-5
Temperature limit for ter-
minating reduced mode
-5 °C, see example on
page 124.
Observe the setting of
coding address "A3"
End temperature raising
F9:-14
Temperature limit for rais-
ing the reduced set room
temperature -14 °C, see
example on page 124.
Set flow temperature increase
FA:20
Raising the set boiler wa-
ter or flow temperature by
20 % when changing
from operation with re-
duced room temperature
to operation with stand-
ard room temperature.
See example on
page 125.
Duration set flow temperature increase
Fb:30
Duration of the set boiler
water or flow temperature
rise (see coding address
"FA") 60 min. See exam-
ple on page 125.
*2
Party mode ends automatically in the "Heating and DHW" operating program
when the system changes over to operation with standard room temperature.
Possible change
F2:0
F2:1
*2
to
F2:12
F8:+10
to
F8:-60
F8:-61
F9:+10
to
F9:-60
FA:0
to
FA:50
Fb:0
to
Fb:150
Code 1
(cont.)
No time limit for party
*2
mode
Time limit adjustable from 1
*2
to 12 h
Temperature limit adjusta-
ble from
+10 to -60 °C
Function disabled
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
Temperature rise adjusta-
ble from 0 to 50 %
Duration adjustable from 0
to 300 min;
1 step ≙ 2 min
65