Hot-swap and Install connection modules

Before turning the switch,
NORMAL
Before turning the switch,
NORMAL
see the manual
BY-PASS
21
see the manual
BY-PASS
24
8
10
31
31
Disconnection:
1. Turn the manual bypass switch
to the intermediate position.
2. Check that LED
is ON before continuing to the BYPASS
21
position.
If LED
is not ON, do not switch to the BYPASS
21
position and call the after-sales support
department.
3. Turn the manual bypass switch
position to the BYPASS position.
The connected equipment is supplied by the AC-power source,
via the manual bypass.
4. Shut down the UPS by pressing button
position).
5. Open the battery circuit breaker(s)
6. Remove the two fixing screws
from the electronic module.
The UPS can be replaced. The connected equipment is
supplied by the AC-power source.
Reconnection:
1. Insert the connection module in the connector
using the two screws
.
31
3. Close the battery circuit breaker(s)
Check that UPS personalization settings still
correspond to the equipment to be supplied
(see section 3.5).
4. Start the UPS by pressing button
5. Check that LED
is ON before turning the manual bypass
20
switch
to the intermediate position.
3
If LED
20
is not ON, do not switch to the
intermediate position and call the after-sales
support department.
6. Turn the manual bypass switch
to the intermediate position.
7. Turn the manual bypass switch
position to the NORMAL position.
The connected equipment is again protected by the UPS.
4. Maintenance
from the NORMAL
3
from the intermediate
3
24
(return to the OFF
.
8
31
and the connection module
and secure
10
8
.
.
24
from the BYPASS position
3
3
from the intermediate
- Page 27
5103321100/AA