4. Maintenance
4.2 UPS replacement
Fault-tolerant connection module
Before carrying out this operation, the supply of power to the connected equipment must be cut.
Page 26 -
5103321100/AA
Disconnection:
1. Shut down the UPS by pressing button
position).
2. Open the battery circuit breaker(s)
3. Remove the two fixing screws
24
from the UPS.
Reconnection:
1. Insert the connection module in the connector
using the two screws
8
2. Close the battery circuit breaker(s)
Check that UPS personalization settings still
correspond to the equipment to be supplied
(see section 3.5).
10
3. Start the UPS by pressing button
The connected equipment is again protected by the UPS.
31
31
24
(return to the OFF
8
.
and the connection module
31
31
.
.
8
24
.
and secure
10