Pulsar EXtreme
1500/2000 VA
2500/3000 VA
installation and user
manual
French
German
Italian
Spanish
Netherlands
5103321100/AA
- Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Pulsar Extreme 1500 VA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MGE UPS Systems Pulsar Extreme 1500 VA

  • Page 1 ™ Pulsar EXtreme 1500/2000 VA 2500/3000 VA installation and user manual French German Italian Spanish Netherlands - Page 1 5103321100/AA...
  • Page 2 Pulsar EXtreme at the end of its service life. To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar EXtreme range, we invite you to visit our web site at Erreur! Signet non défini. or contact your MGE UPS SYSTEMS representative.
  • Page 3: Safety Rules

    Safety Safety rules Safety of persons A UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC-power source. Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
  • Page 4 Foreword Using this document Information may be found primarily by consulting: the contents; the index. Pictograms Important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audio indication. In the illustrations on the following pages, the symbols below are used: LED off.
  • Page 5: Table Of Contents

    Contents Presentation Pulsar EXtreme range ......................... 7 Connection modules ........................8 Fault tolerant ........................... 8 Hot swap ............................8 Install ............................... 8 Back ............................. 9 Control panel ..........................10 Installation Unpacking and checks ....................... 11 "Tower" model ..........................11 "Rack" model ..........................11 Installation (rack version) ......................
  • Page 6 Contents Failure of AC input power and operation on battery power ............ 20 Transfer to battery power ......................20 Threshold for the low-battery shutdown warning ................20 End of backup time ........................20 Sleep mode ........................... 20 Return of AC input power ......................20 Personalization ...........................
  • Page 7: Presentation

    1. Presentation 1.1 Pulsar EXtreme range Tower model Dimensions in mm (H x W x D) EXtreme 1500 to 3000 443 x 173 x 465 Weight in kg EXtreme 1500 to 2000 EXtreme 2500 to 3000 Rack model Dimensions in mm (H x W x D) EXtreme 1500 to 3000 177 (4U) x 483 x 462...
  • Page 8: Connection Modules

    1. Presentation 1.2 Connection modules Fault tolerant socket for connection to AC-power source. outlets for direct connection to protected equipment. manual bypass switch. input terminal block with cable clamp. output terminal block with cable clamp. Hot swap Install Page 8 - 5103321100/AA...
  • Page 9: Back

    1. Presentation 1.3 Back slot for communications-card option. battery module connector. battery circuit breaker. rating plate. connector for connection modules. RS232 communications port. - Page 9 5103321100/AA...
  • Page 10: Control Panel

    1. Presentation 1.4 Control panel Alarms % battery % load remaining UPS overload 100% 100% electronics fault battery fault ambient temp. > 40°C hold down to display percent load. lamp test or buzzer OFF. operation on manual bypass. operation in ECO mode. operation in ON-LINE mode.
  • Page 11: Unpacking And Checks

    2. Installation 2.1 Unpacking and checks Tower model RS 232 communications cable. "Solution Pac" CD ROM. "UPS Driver" diskette for UPS personalization. documentation. electrical power cord (except INSTALL version). - Page 11 5103321100/AA...
  • Page 12 2. Installation Rack model RS 232 communications cable. "Solution Pac" CD ROM. "UPS Driver" diskette for UPS personalization. documentation. electrical power cord (except INSTALL version). telescopic rails for mounting in 19" bay with mounting hardware. Page 12 - 5103321100/AA...
  • Page 13: Installation (Rack Version)

    2. Installation 2.2 Installation (rack version) Rack mounting diagram with rails. The rails and the necessary mounting hardware are supplied with the UPS in the package. - Page 13 5103321100/AA...
  • Page 14: Connection To The Rs 232 Communications Port (Optional)

    2. Connect the RS 232 communications cable to the RS 232 communications port on the UPS. The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software. Pin-out diagram for the RS 232 communications port on the UPS.
  • Page 15: Securing And Connecting The Connection Modules

    2. Installation 2.5 Securing and connecting the connection modules Securing the connection modules Insert the connection module in the connector 1. Secure the connection module to the UPS using the two screws Fault tolerant Before carrying out any connections, check that the battery circuit breaker is OFF and that the electrical power cord to the AC-power source is disconnected.
  • Page 16: Hot Swap

    2. Installation Hot swap Before carrying out any connections, check that the battery circuit breaker is OFF and that the electrical power cord to the AC-power source is disconnected. Connection of equipment to outlets Plug your equipment into the outlets Connection of equipment to a terminal block: This type of connection must be carried out by qualified electrical personnel.
  • Page 17: Install

    2. Installation Install This type of connection must be carried out by qualified electrical personnel. Before carrying out any connections, check that the battery circuit breaker is OFF and that the upstream protection devices (AC distribution system) are open (OFF). The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.
  • Page 18: Operation Operating Mode

    3. Operation 3.1 Operating mode ON-LINE mode This is the standard operating mode, set by default in the factory. It makes use of electronic double conversion of the input power. Two possible cases: is ON: AC input power is available. Power is drawn from the distribution system and supplied to the protected equipment via the UPS.
  • Page 19: Start-Up

    3. Operation 3.2 Start-up The protected equipment connected to the UPS can be energized, whether AC input power is available or not. Prior to initial start-up, check the UPS voltage settings. If the protected equipment voltage is other than 230 V / 50 Hz, the UPS settings must be modified using the "UPS Driver" software (see section 3.5).
  • Page 20: Failure Of Ac Input Power And Operation On Battery Power

    3. Operation 3.4 Failure of AC input power and operation on battery power AC input power is not available, the battery steps in to supply the protected equipment. Transfer to battery power The AC-power source is outside tolerances, LED is ON, the buzzer beeps three times.
  • Page 21: Personalization

    3. Operation 3.5 Personalization Function Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port). Check that the RS 232 cable is correctly connected and that the battery circuit breaker is closed.
  • Page 22: Battery" Tab

    3. Operation "Battery" tab Personalizable function Default setting Options Once a week "Battery test" intervals Every day Once a month No test "Low-battery shutdown warning" threshold 20% remaining battery 40% remaining battery backup time backup time Charger Standard CLA (2, 4 or 8 hours) "Output"...
  • Page 23: Eco Mode" Tab

    3. Operation "ECO mode" tab ECO mode is not possible unless it has first been authorized using the "UPS Driver" software Personalizable function Default setting Options ECO mode authorization Disabled Enabled (click to check) (not authorized) The upper threshold (max. voltage) is between the maximum authorized voltage for transfer to Authorized voltage range for 200 V to 240 V...
  • Page 24: Maintenance Troubleshooting

    4. Maintenance 4.1 Troubleshooting If any of LEDs flash, there is a operating anomaly or an alarm. 14 15 16 If a LED flashes, the bargraph data is no longer displayed. Troubleshooting not requiring MGE after-sales support Indication Signification Remède flashes and the buzzer UPS overload.
  • Page 25 4. Maintenance Troubleshooting requiring MGE after-sales support Indication Signification Correction flashes and the buzzer UPS electronics have detected a UPS For UPSs equipped with Hot beeps. fault. swap or Install connection Depending on the UPS personalization modules, follow the UPS parameters (see section 3.5), there are replacement procedure (see two possibilities:...
  • Page 26: Ups Replacement

    4. Maintenance 4.2 UPS replacement Fault-tolerant connection module Before carrying out this operation, the supply of power to the connected equipment must be cut. Disconnection: 1. Shut down the UPS by pressing button (return to the OFF position). 2. Open the battery circuit breaker(s) 3.
  • Page 27: Hot-Swap And Install Connection Modules

    4. Maintenance Hot-swap and Install connection modules Disconnection: Before turning the switch, see the manual 1. Turn the manual bypass switch from the NORMAL to the intermediate position. 2. Check that LED is ON before continuing to the BYPASS NORMAL BY-PASS position.
  • Page 28: Environment

    It was manufactured in a factory certified ISO 14001. UPS recycling at the end of service life: MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your branch office).
  • Page 29: Glossary

    6. Appendices 6.1 Glossary Authorized voltage The range of voltage supplied by the AC-power source within which the UPS range for operation in ECO can operate in ECO mode. In ECO mode, the equipment connected to the in ECO mode UPS is supplied directly by the AC-power source, via the automatic bypass.
  • Page 30 6. Appendices Frequency-regulation rate The rate at which the UPS frequency is synchronized with that of the AC-power source. Two possible cases: 1. The installation comprises a single UPS. The frequency-regulation rate is set to "Standard". 2. The installation comprises two UPSs connected in series. The AC-power source supplies power to the first UPS which in turn supplies the second UPS.
  • Page 31: Index

    6. Appendices 6.2 Index AC power LEDs Failure ............20 Lamp test ............10 Frequency tolerance ........22 Rated frequency ..........22 Rated voltage ..........22 Mode Return ............20 ECO mode .......... 10-18-23 Bargraph .............. 19 Overload ............ 10-22-24 Battery Battery test ............
  • Page 32 SYSTEMS N o t h i n g w i l l s t o p y o u n o w 140, Avenue Jean Kuntzmann ZIRST - Montbonnot St Martin 38334 - ST ISMIER CEDEX - FRANCE www.mgeups.com 5103321100/AB Page 32 - 5103321100/AA...