7.4.7 Noise production
The average noise level measured at 1-m distance
around the boiler modules is < 63 dBA at full output,
avoiding the need for additional acoustic measures.
7.5 Multiple boiler installation
The Remeha Gas 610 ECO is available up to 1146
kW. For greater outputs the Remeha Gas 610 can be
installed in a multiple boiler installation. The narrow
width and depth of the boiler provides a high output
within a small floor area (see fig. 05). Advice and sche-
matic drawings are available on request, contact Broag
Technical Dept.
fig. 11 Sample hydraulic diagram cascade configuration
pdf
Remeha Gas 610 ECO
1.
OpenTherm or rematic
controller
2.
boiler pump
3.
safety valve
4.
non return valve
6.
isolating valve
7.
automatic air vent
8.
low loss header
9.
drain cock
10.
system pump
11.
expansion vessel system
12.
flow temperature sensor
14.
outside temperature sensor
20
modulating cascade
®