REMEHA 610 ECO Technical Information page 37

High efficiency condensing boiler with low nox emission
Hide thumbs Also See for 610 ECO:
Table of Contents

Advertisement

Code
Description
t
37 Shut-off code (see table 23)
1
Operating code, at shut-off interven-
2
03
tion (section 12.1)
Flow temperature, at shut-off interven-
3
53
tion
Return temperature, at shut-off inter-
4
40
vention
Flue gas temperature, at shut-off inter-
5
58
vention
Boiler block temperature, at shut-off
6
63
intervention
Time from shut-off intervention (with
7 + 8 00
PC software only)
Ionisation level (analog), at shut-off
9
18
intervention
Operating hours (hundred thousands
a
11
and ten thousands)
Operating hours (thousands and hun-
b
80
dreds)
26 Operating hours (tens and units)
c
Fan speed at shut-off intervention
d
26
(thousands and hundreds)
Fan speed at shut-off intervention
e
67
(tens and units)
table 14 Shut-off mode in service level
The letters and numbers in the code window and the t
window are explained in appendix 16.2.
12.5 Counter mode (1, , and .) (service level)
12.5.1 General
The boiler module control records various data on the
combustion trend of the boiler module. This data can
be read out in counter mode. The following data can be
read out:
- Hours run
- Number of successful ignition attempts
- Total number of start attempts
- Number of shunt pump operating hours
- Number of shunt pump starts
- Number of internal resets (control unit)
- Number of hours energised (control unit)
12.5.2 Reading out counter mode
First enter the service code c 12 (see section 13.2).
Press the m key until the required code (see table 15)
appears in the code window.
Hours run
1
Number of successful ignition attempts
2
Total number of start attempts
3
Number of shunt pump operating hours
4
Number of shunt pump starts
5
Number of automatic corrections (control
6
unit)
Number of hours energised (control unit)
7
table 15 Counter mode codes
The counter has 6 digits. The code window displays the
following (in sequence):
code figure, ,, . with a value in the t window.
Meaning of readout in t window
Code
Total number or total number of hours in
figure
hundred thousands and ten thousands
Total number or total number of hours in
,
thousands and hundreds
Total number or total number of hours in
.
tens and units
table 16 Counter mode readout
Example:
code window
t window
1
21
,
57
.
53
This means 215753 Hours run
37
value
210000
5700
53

Hide quick links: