4.2 Technical data

Boiler type
General
Boiler control options
Nominal output Pn (80/ 60°)
Nominal output Pn (50/ 30°)
Nominal input Qn (GCV/ Hs)
Nominal input Qn (NCV/ Hi)
Efficiency (Hi)
Combustion (Hi) at 80/ 60°
Heat to water (Hi) at 80/ 60°
Standing losses (T
= 45°)
average
Annual efficiency (Hi)
Gas and flue gas side
Gas category
Inlet pressure gas (boiler running)
Gas consumption
NO
emission* (DIN 4702 p.8; annual
X
emissions)
NO
emission* (DIN 4702 p.8; annual
X
emissions, O
= 0%, dry)
2
Residual fan duty
Flue gas mass
Flue gas temperature at 80/ 60°
Type classification due to discharging flue
gasses
Water side
Flow temperature
Operating pressure
Water contents
Water resistance at 11° dT
Water resistance at 20° dT
Unit
-
min
kW
max kW
min
kW
max kW
min
kW
max kW
min
kW
max kW
%
%
%
%
-
min
mbar
max mbar
m
/ h
3
0
mg/ kWh
ppm
Pa
min
kg/ h
max kg/ h
min
°
max °
-
High Limit
°
Operating
°
min
bar
max PMS
bar
litres
mbar (kPa)
mbar (kPa)
10
Remeha Gas 610 ECO
Remeha Gas 610 ECO
2 x 6 sec-
2 x 7 sec-
tions
tions
Modulating, 2-stage or 4-stage
87
123
654
790
94
131
706
854
101
142
744
896
91
128
672
808
up to 99
up to 98,5
< 0.3
108,9
Natural gas only
17
100
74
86
< 60
< 35
130
153
215
1130
1360
57
65
B23, C33, C43, C53, C63, C83
110
20 - 90
0.8
120
142
364 (36.4)
397 (39.7)
110 (11)
120 (12)
2 x 8 sec-
2 x 9 sec-
tions
tions
122
148
924
1062
130
156
998
1146
141
170
1046
1196
127
153
942
1078
100
114
214
257
1586
1814
6
164
186
364 (36.4)
413 (41.3)
110 (11)
125 (12.5)