REMEHA 610 ECO Technical Information page 47

High efficiency condensing boiler with low nox emission
Hide thumbs Also See for 610 ECO:
Table of Contents

Advertisement

15
INSPECTION AND MAINTENANCE INSTRUCTIONS
15.1 General
The Remeha Gas 610 ECO has been designed to need
minimum maintenance, but to ensure optimum efficiency
we advise that once a year each boiler module should
be checked and if necessary cleaned and reset.
All service and maintenance must be carried out by a
qualified Engineer with the relevant training and certifi-
cation (ie CORGI - ACOPS - etc.).
15.2 Cooling mode
This mode enables maintenance on the burner and/ or
the heat exchanger to be carried out more efficiently. In
this mode, the fann runs at maximum speed for two min-
utes, which cools down the boiler module rapidly. When
this mode is active, the system does not respond to heat
demands.
g
Important!!
This mode can only be activat-
ed if there is no heat demand on the boiler module.
The code c[l indicates that the mode is active (
c[l for cooling).
The mode is activated by pressing the s and [+] keys
simultaneously (during normal operating status with no
heat demand).
The mode can be terminated prematurely by pressing
the [+] and [-] keys simultaneously.
15.3 Annual Inspection
The annual inspection of the Remeha Gas 610 (per
module) as follows:
- Check combustion characteristics, full and part load
(see section 10.1).
Note: When checking combustion the C0
be in accordance with the values in table 11 with a
tolerance of +/- 0.5%. If the levels are outside these
tolerances, adjustment to the levels must be made in
accordance with a tolerance of +/- 0.15%.
- Check flue gas temperature. If flue gas temperature
is more than 30°C above the boiler return water tem-
perature the heat exchanger must be cleaned (see
par. 15.4.5).
- Check/clean the condensate siphon (refill with clean
water).
- Check for leaks (waterside, flue gas side and gas
soundness).
- Check flue and air inlet system is clear and gas/
water tight.
- Check system pressure.
- Check control settings.
- Check boiler parameters.
- Check ionisation level, minimum 3 μA dc (see 12.2,
parameter G).
If ionisation level < 3 μA dc or not present, check:
- Is flame shape stable and colour as described in
commissioning instructions.
- Check ignition probe earth.
- Check condition of ignition/ ionisation probe replace if
necessary.
- Replace electrode at least every 2 years.
- Clean any oxides/deposits with sandpaper or fine
emery cloth.
- Check shape of probe and ignition gap, i.e. 3 to 4 mm
(see fig. 35).
- Check temperature sensors for resistance values
against fig. 27 (humidity on sensors).
- Check and clean if necessary the gas filter.
-
Check air box and dirt trap (see section 15.4.1).
fig. 27 Sensor resistance graph
15.4
If during the annual inspection combustion results indi-
levels should
cate that the boiler module is no longer operating at the
2
optimum level, additional maintenance should be carried
out as follows:
NOTE:
Please ensure that the gas supply and mains power
supply is isolated before any maintenance work is car-
ried out on the boiler module.
Care should be taken when stripping the boiler module
for maintenance making sure that all parts nuts, wash-
ers and gaskets etc. are kept safe, clean and dry for
re-assembly.
Following maintenance/ cleaning, the boiler module
should be re-assembled in the reverse order re-placing
gaskets and joints where found necessary.
All general cleaning should be carried out with
compressed air, a soft brush or damp cloth to avoid
damaging components. (Solvents must not be
used).
Remove front and end casing panels – lift casing panel
slightly upwards and tilt toward you lift again clear of the
bottom rail.
47
Maintenance

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents