12
OPERATING MODE
g
Important!!
The subjects described in this
chapter apply to each boiler module.
12.1 Operating mode (x [[)
During normal operation the code-display shows the
status (position in cycle) of the boiler module, with the
t -display indicating the actual flow temperature.
The digits or letters in the code-display have the follow-
ing meaning:
Code
Description
Standby; there is no heat demand from
0
control system
Pre-ventilation (pre-ventilation time 30 sec-
1
onds, post ventilation time 3 seconds)
Ignition
2
The burner is firing (flame detection)
3
N/a
4
Waiting mode; check for sufficient air flow
using fan and air pressure differential sen-
5
sor (LDS)
Control stop (burner off + post ventilation) :
- flow temperature T1 > setpoint + 5°
- flow temperature T1 > desired setpoint
modulating control + 5°
6
- flow temperature T1 > parameter 1
- difference flow T1 and return T2 > 10°
(factory setting); Starting condition is [
10 °.
Code
Description
Flow temperature (°)
!
Return temperature (°)
@
Flue gas temperature (°)
#
N/a
$
Heat exchanger temperature (°)
%
Flow temperature (set point, °)
^
Heat demand status (1
&
sure differential sensor (LDS, 2
Switch-on temperature for central heating
*
operation (°)
Requested (and permitted by control) out-
put (%) is displayed, irrespective of control
(
setting.
Read-out range/comments
actual value
actual value
actual value
actual value
Calculated value
0x = on/off-contact open
1x = on/off contact closed
digit) and air pres-
st
x0 = air pressure differential sensor open
digit)
nd
x1 = air pressure differential sensor
closed
demanded value
00 - )0 (=100%)
demanded value
35
End of heating demand, pump run on time.
During cycling prevention delay-time the
7
boiler module will remain in state 7 and
will not react to heat demand.
N/a
8
Shut-off mode (see section 12.4)
b
Forced full load (HIGH)
h
Forced part load (LOW)
l
Gas leakage control
t
Burner cooling
c[l
table 12 Operating codes
12.2 Read-out mode (X [[)
Read-out mode is used to display various values. Press
the m key until ! appears in the code window (dot
flashes). Select the required code using the s key.
Read-out
(e.g.)
80
70
85
75
84
11
40
90