Monitoring The Running Status -- Menu #3 "Drive Monitoring - Fuji Electric Frenic Mega Series User Manual

High performance, multifunction inverter
Hide thumbs Also See for Frenic Mega Series:
Table of Contents

Advertisement

7.4.4
Monitoring the running status
Menu #3 "Drive Monitoring" in Programming mode allows you to monitor the running status during
maintenance and test running.
Page # in
operation
Item
guide
Output frequency
Output frequency
1
Output current
Output voltage
Calculated torque
Reference frequency
Running direction
Current limit
Undervoltage
Voltage limit
2
Torque limit
Speed limit
Motor selected
Drive control
Motor speed
Load shaft speed
3
Line speed
Constant peripheral speed
control monitor
PID command value
PID feedback amount
4
PID output value
-- Menu #3 "Drive Monitoring" --
Table 7.11 Drive Monitoring Items
Symbol
Fot1
Output frequency (before slip compensation)
Fot2
Output frequency (after slip compensation)
Iout
Output current
Vout
Output voltage
TRQ
Calculated output torque generated by motor
Fref
Frequency specified by a frequency command
FWD
Forward
REV
Reverse
(Blank)
Stopped
IL
Current limiting
LU
Undervoltage detected
VL
Voltage limiting
TL
Torque limiting
SL
Speed limiting
M1-M4 Motor 1 to 4
VF
V/f control without slip compensation
DTV
Dynamic torque vector control
VF-SC
V/f control with slip compensation
VF-PG
Dynamic torque vector control with speed sensor
VC-SL
Vector control without speed sensor
VC-PG
Vector control with speed sensor
SYN
(Output
frequency
LOD
Output frequency (Hz)
LIN
Output frequency (Hz)
Actual peripheral speed under constant peripheral speed
LSC
control
SV
The PID command value and PID feedback amount are
displayed after conversion to the virtual physical values (e.g.,
temperature or pressure) of the object to be controlled using
function code E40 and E41 data (PID display coefficients A and
PV
B).
Display value = (PID command value or feedback amount)
(Coefficient A - B) + B
PID output value, displayed in % (assuming the maximum
MV
frequency (F03) as 100%).
7-25