2.4.3 Terminal arrangement and screw specifications

2.4.3.1

Main circuit terminals

The tables and figures given below show the screw specifications and wire sizes. Note that the terminal
arrangements differ depending on the inverter types. In each of the figures, two grounding terminals ( G)
are not exclusive to the power supply wiring (primary circuit) or motor wiring (secondary circuit).
Use crimp terminals covered with an insulation sheath or with an insulation tube.
The recommended wires for main circuit terminals are selected according to the sizes conforming to
UL508C.
Inverter type
Three-phase
Three-phase
230 V
460 V
FRNF50G1S-2U
FRNF50G1S-4U
FRN001G1S-2U
FRN001G1S-4U
FRN002G1S-2U
FRN002G1S-4U
FRN003G1S-2U
FRN003G1S-4U
FRN005G1S-2U
FRN005G1S-4U
FRN007G1 -2U
FRN007G1 -4U
FRN010G1 -2U
FRN010G1 -4U
FRN015G1 -2U
FRN015G1 -4U
FRN020G1 -2U
FRN020G1 -4U
FRN025G1 -2U
FRN025G1 -4U
FRN030G1 -2U
FRN030G1 -4U
FRN040G1 -2U
FRN040G1 -4U
FRN050G1 -4U
FRN060G1 -4U
FRN050G1 -2U
FRN075G1 -4U
FRN100G1 -4U
FRN060G1 -2U
FRN075G1 -2U
FRN125G1S-4U
FRN100G1 -2U
--
FRN150G1S-4U
--
FRN200G1S-4U
FRN125G1S-2U
--
--
FRN250G1S-4U
--
FRN300G1S-4U
FRN350G1S-4U
FRN150G1S-2U
FRN450G1S-4U
--
FRN500G1S-4U
--
FRN600G1S-4U
--
FRN700G1S-4U
--
FRN800G1S-4U
--
FRN900G1S-4U
--
FRN1000G1S-4U
Note: A box ( ) in the above table replaces S or H depending on the enclosure.
When the inverter power is ON, a high voltage is applied to the following terminals.
Main circuit terminals: L1/R, L2/S, L3/T, P1, P(+), N(-), DB, U, V, W, R0, T0, R1, T1, AUX-contact (30A, 30B,
30C, Y5A, Y5C)
Insulation level
Main circuit ― Enclosure : Basic insulation (Overvoltage category III, Pollution degree 2)
Main circuit ― Control circuit : Reinforced insulation (Overvoltage category III, Pollution degree 2)
Relay output ― Control circuit : Reinforced insulation (Overvoltage category II, Pollution degree 2)
An electric shock may occur.
Table 2.2 (1) Screw Specifications
Main circuit
terminals
Refer to:
Tightening
Screw
Screw
torque
size
size
lb-in (N·m)
Figure A M3.5
10.6 (1.2)
M3.5
Figure B
M4
15.9 (1.8)
M4
Figure C
M5
31.0 (3.5)
M5
Figure D
M6
51.3 (5.8)
M6
Figure E
M8
119 (13.5)
M8
Figure F
M10
239 (27)
Figure G
Figure M
Figure H
Figure I
M12
425 (48)
M10
Figure J
Figure K
Figure L
2-31
2.4 Terminal Specifications
Screw specifications
Auxiliary control
Grounding
power input
terminals
terminals
[R0, T0]
Tightening
Tightening
Screw
torque
torque
size
lb-in (N·m)
lb-in (N·m)
10.6 (1.2)
--
--
15.9 (1.8)
31.0 (3.5)
51.3 (5.8)
119 (13.5)
M3.5
10.6 (1.2)
239 (27)
Auxiliary fan
power input
terminals
[R1, T1]
Tightening
Screw
torque
size
lb-in (N·m)
--
--
M3.5
10.6 (1.2)