Page 72
217
Invalid Run
stabilization
time setting
218
Invalid Stack
limit enable
setting
219
Invalid Stack
limit response
setting
220
Unconfi gured
Delta T limit
setpoint setting
221
Unconfi gured
DHW (Domestic
Hot Water) high
limit setpoint
setting
222
Unconfi gured
Outlet high limit
setpoint setting
223
Unconfi gured
Stack limit
setpoint setting
224
Invalid DHW
(Domestic Hot
Water) demand
source setting
225
Invalid Flame
threshold setting
226
Invalid Outlet
high limit
setpoint setting
227
Invalid DHW
(Domestic Hot
Water) high
limit setpoint
setting
228
Invalid Stack
limit setpoint
setting
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.
L
1. Return to Confi guration mode and recheck selected parameters,
reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.